Square D HDL36100 600 Volt 100 Amp Molded Case Circuit Breaker

MFG Part #: HDL36100
Brand Name: Square D by Schneider Electric
UPC: 78590183993 78590183993
Online Part #: 82320

Description

The PowerPact™ H-frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. H-frame circuit breakers are available with either thermal-magnetic or Micrologic™ electronic trip units. The amperage ratings of the thermal trip elements are calibrated at 104°F (40°C) free air ambient temperature. Per the National Electric Code® (NEC®) and the Canadian Electrical Code, standard circuit breakers may only be applied continuously at up to 80% of their rating. This PowerPact H circuit breaker is a 3-pole and has a rated current of 100A. With a breaking capacity of 14kA@600VAC operational voltage and a continuous current rating of 80%. This circuit breaker has a thermal-magnetic trip unit. This is a unit mounted breaker. This breaker complies to UL listed, CE, CSA & IEC standards. Dimensions for this breaker are 6.4 in(H), 4.12 in(W), 4.36 in(D), and has an ambient temperature of 40 °C. This product comes with an 18 months warranty.

Detailed Information

Make and Model

Online Part #: 82320
MFG Name: Schneider Electric

Specification

Width: 4.0945 in
Frequency Rating: 50/60 Hz
Sub Brand: POWERPACT
Height: 6.417 in
Frame: H-FRAME
Trip Type: THERMAL-MAGNETIC
Type: Product, MOLDED CASE CIRCUIT BREAKER
Number of Poles: 3 Pole
Trip Range: HOLD: 900A - TRIP: 1700A
Length: 86 MM
Brand Name: Square D by Schneider Electric
Amperage Rating: 100A
Application: PROVIDES OVERLOAD AND SHORT CIRCUIT PROTECTION
Voltage Rating: 600//250 VAC//VDC
Standards: UL LISTED - CSA CERTIFIED - IEC RATED - CCC
Connection: LINE: LUG - LOAD: LUG
Interrupt Rating: 25KA@240VAC - 18KA@480VAC - 14KA@600VAC - 20KA@250VDC
Operating Temperature: -13F AND 158F (-25 C AND +70 C)
Prop65_Warning: WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.p65warnings.ca.gov